HCFC
- R409A
A blend
of R-22, R-142b, and R-124, intended for retrofitting R-12
refrigeration systems. The pressure and system capacity match
R-12 when the blend is running in a 10F to 20F evaporator,
and there is typically 13F temperature glide in the evaporator.
Applications: direct expansion refrigeration and air conditioning
systems designed for R-12 or R-500; good success in any size
system, minor adjustment of controls needed. Discharge pressure
and temperature increases compared to R-12, which may be a
problem in
very hot ambient conditions. Capacity holds well into lower application temperatures
(-30F). R-409A mixes well with mineral oil down to 0F. As a result it may not
be necessary to change oil in systems which do not run colder than 0F in the
evaporator (below that alkylbenzene should replace some mineral oil). |