BANKING & RECLAMATION - Recovered Refrigerant Acceptance Specifications 

Only Fluorocarbon refrigerants from refrigeration and air conditioning systems are acceptable. Halons will not be accepted. Fluorocarbons from other applications such as solvents or cleaning agents are NOT acceptable.

Non-fluorocarbon refrigerants such as ammonia, methylene chloride, propane, ethane, sulfur dioxide, etc., are NOT acceptable. Also, fluorocarbon refrigerants contaminated with hydrocarbons in excess of 0.5% by weight (total hydrocarbons) will not be accepted.

Only one grade of refrigerant per container is acceptable. Refrigerant must be shipped in DOT approved recovery containers. Refer to ARI Guideline K.

Containers must not exceed the Maximum Allowable Gross weight as specified in NRI's Cylinder Weight Chart. Overfilled containers will be subject to a handling fee.

Refrigerant contaminants are acceptable with the following limits:

PURITY
99.5 % for R502 minimum (excluding oil content) 99% for all other CFCs, HCFCs and HFCs

COMPONENT RATIOS
Must be within ARI 700 specifications for any refrigerant containing two or more components

OIL
Not to exceed 20% by weight in R11, R113 & R123 Not to exceed 10% by weight in all other refrigerants

WATER
Water exceeding saturation point of refrigerant requires special processing to separate the free standing water from the refrigerant; fee will be charged for each pound of free water

ACID
pH must be greater than 2.0 and less than 12.0; pH level between 2.0 - 5.0 requires special handling to neutralize acid in the material; fee will be based on the gross weight of material

DYES
Not to exceed 1 % by weight